The ada standards do not require this grab bar but allow a second grab bar to be within the 12 clearance above the horizontal grab bar 609 3 if there is a separation of 1 min.
Ada vertical grab bar height.
The bottom of a vertical bar in transfer showers must be 3 6 inches over the horizontal bar on the wall.
Bottom of the bar located 39 990 mm minimum and 41 1040 mm maximum above the floor.
A 42 inches 1065 mm minimum length grab bar is required on the side wall spaced a maximum of 12 inches 305 mm from the back wall and extending a minimum of 54 inches 1370 mm from the back wall at a height of 33 36 inches 840 915 mm.
Vertical grab bar requirements a vertical grab bar 18 455 mm minimum in length mounted along the side wall.
Two grab bars shall be installed on the back wall one located in accordance with 609 4 and the other located 8 inches 205 mm minimum and 10 inches 255 mm maximum above the rim of the bathtub.
Vertical grab bar icc a117 1 standard the icc a117 1 standard for accessible and usable buildings and facilities which is referenced by the international building code requires an 18 min.
In figure 29 b a 42 inch 1065 mm minimum length grab bar is required to the side of the water closet spaced 12 inches 305 mm maximum from the back wall and extending a minimum of 54 inches 1370 mm from the back wall at a height between 33 and 36 inches 840 915 mm.
Each grab bar shall be installed 15 inches 380 mm maximum from the head end wall and 12 inches 305 mm maximum from the control end wall.
The toilet paper dispenser shall be mounted below the grab bar at a minimum height of 19 inches 485 mm.